7.5 Set and Reset

Another function that is often available is the ability to set and reset an internal relay. The set instruction causes the relay to self-hold, that is, latch. It then remains in that condition until the reset instruction is received. The term flip-flop is often used. Figure 7.12 shows the IEC 1131-3 standards for such coils. The SET coil is switched on when power is supplied to it and remains set until it is RESET. The RESET coil is reset to the off state when power is supplied to it and remains off until it is SET.

Figure 7.13 shows an example of a ladder diagram involving such a function. Activation of the first input, X400, causes the output Y430 to be turned on and set, that is, latched. Thus if the first input is turned off, the output remains on. Activation of the second input, X401,causes the output Y430 to be reset, that is, turned off and latched off. Thus the output Y430 is on for the time between X400 being momentarily switched on and X401 being momentarily switched

on. Between the two rungs indicated for the set and reset operations, there could be other rungs for other activities to be carried out, with the set rung switching on an output at the beginning of the sequence and off at the end.

The programming instructions for the ladder rungs in the program for Figure 7.13 are:

LD X400 S Y430 Other program rungs are:

LD X401 R Y430

With a Telemecanique PLC, the ladder diagram would be as shown in Figure 7.14 and the

programming instructions would be:

L I0,0 S O0,0 L I0,1 R O0,0

With an Allen-Bradley PLC, the terms latch and unlatch are used. Figure 7.15 shows the ladder diagram.

The SET and RESET coil symbols are often combined in a single box symbol. Figure 7.16 shows the equivalent ladder diagram for the set-reset function in the preceding figures with a Siemens PLC. The term memory box is used by them for the SET/RESET box, and the box shown is termed an SR or reset priority memory function in that reset has priority.With set priority (RS memory box), the arrangement is as shown in Figure 7.17.The programming instructions (F indicates an internal relay) for reset priority are: A I0.0 S F0.0 A I0.1 R F0.0 A F0.0 1?4 Q2.0

Toshiba uses the term flip-flop, and Figure 7.18 shows the ladder diagram.

Figure 7.19 shows how the set-reset function can be used to build the pulse (one-shot)function described in the previous section. Figure 7.19a shows it for a Siemens PLC(F indicates internal relay) and Figure 7.19b for a

  • 收藏
  • 违规举报
  • 版权认领
下载文档10.00 元 加入VIP免费下载
推荐下载
本文作者:...

共分享92篇相关文档

文档简介:

7.5 Set and Reset Another function that is often available is the ability to set and reset an internal relay. The set instruction causes the relay to self-hold, that is, latch. It then remains in that condition until the reset instruction is received. The term flip-flop is often used. Figure 7.12 shows the IEC 1131-3 standards for such coils. The SET coil is switched on when power is sup

× 游客快捷下载通道(下载后可以自由复制和排版)
单篇付费下载
限时特价:10 元/份 原价:20元
VIP包月下载
特价:29 元/月 原价:99元
低至 0.3 元/份 每月下载150
全站内容免费自由复制
VIP包月下载
特价:29 元/月 原价:99元
低至 0.3 元/份 每月下载150
全站内容免费自由复制
注:下载文档有可能“只有目录或者内容不全”等情况,请下载之前注意辨别,如果您已付费且无法下载或内容有问题,请联系我们协助你处理。
微信:fanwen365 QQ:370150219
Copyright © 云题海 All Rights Reserved. 苏ICP备16052595号-3 网站地图 客服QQ:370150219 邮箱:370150219@qq.com